The Dayliff DGJ diesel generators, known for their robustness and high quality, are designed for continuous duty in a wide range of power supply applications. These generators find applications in various industries and settings due to their features and capabilities. Some of the common applications for Dayliff DGJ generators include:
1. Commercial and Industrial Power Backup: The DGJ generators are ideal for providing backup power in commercial and industrial settings. They can ensure uninterrupted power supply during mains power outages, preventing disruptions to critical operations, machinery, and equipment.
2. Construction Sites: The generators are commonly used in construction sites where reliable and continuous power is required. They can provide power for construction equipment, tools, lighting, and other electrical needs on-site.
3. Remote and Off-Grid Locations: DGJ generators are suitable for remote areas or off-grid locations where access to mains power is limited or unavailable. They can be used in remote construction projects, mining operations, agricultural sites, or rural communities, providing a dependable source of power.
4. Healthcare Facilities: Hospitals, clinics, and medical centers rely on continuous power supply for critical equipment, medical devices, and life-saving systems. The DGJ generators can serve as reliable backup power sources, ensuring that healthcare facilities can operate seamlessly during power outages.
5. Telecommunication and Data Centers: Telecommunication towers, data centers, and communication infrastructure require a stable and uninterrupted power supply. The DGJ generators provide backup power in the event of mains power failures, ensuring uninterrupted communication and data services.
6. Residential Backup Power: The generators are suitable for residential backup power applications, providing households with power during blackouts. They can keep essential appliances, lighting, and heating or cooling systems operational, ensuring comfort and safety.
7. Events and Entertainment: The DGJ generators are commonly used for outdoor events, concerts, festivals, or exhibitions. They can power stages, lighting, sound systems, food stalls, and other event infrastructure, ensuring a seamless and uninterrupted experience.
8. Agriculture and Farming: Farms and agricultural operations often require power for irrigation systems, machinery, and livestock facilities. The generators can provide a reliable power source, ensuring continuous operation and productivity in agricultural settings.
Overall, the Dayliff DGJ generators are versatile and reliable power solutions for a wide range of applications. Their robust construction, advanced control features, and dependable performance make them suitable for continuous duty and standby power requirements in commercial, industrial, residential, and remote settings.
TECHNICAL DATA
Generator Model |
DGPJ07 |
DGPJ12 |
DGPJ16 |
DGJP24 |
DGJP36 |
DGJP48 |
DGJP64 |
DGJP80 |
DGJP108 |
Prime/Standby Power Output |
kVA |
9/10 |
15/16.5 |
20/22 |
30/33 |
45/50 |
60/66 |
80/88 |
100/110 |
135/150 |
kW |
7/8 |
12/13.2 |
16/18 |
24/26 |
36/40 |
48/52.8 |
64/70.4 |
80/88 |
108/120 |
Engine Data |
Perkins Model |
403A11G1 |
403A15G2 |
404A22G1 |
1103A33G3 |
1103A33TG1 |
1103A33TG2 |
1104A44TG2 |
1104C44TAG2 |
1106A70TG1 |
Rated Power @ 1500rpm (kW) |
9 |
14 |
19 |
29 |
42 |
55 |
73 |
94 |
123 |
Aspiration |
Natural |
Turbocharged |
No. of cylinders |
3 |
3 |
4 |
3 |
4 |
6 |
Displacement (L) |
1.1 |
1.5 |
2.2 |
3.3 |
4.4 |
7.0 |
Fuel Consumptions (litres/hr) |
75% load |
2 |
3.1 |
4 |
5 |
8 |
10 |
14 |
17 |
23 |
100% load |
3 |
|
5.3 |
7 |
11 |
14 |
19 |
236 |
30 |
Fuel Tank Size (litres) |
51 |
85 |
110 |
260 |
Alternator Data |
Alternator Type |
Self excited 4 pole (1500rpm) single bearing, brushless |
Output Voltage |
3x415V |
Voltage Regulation |
AVR±1.0% with 4% engine governing |
Insulation Class |
H |
Protection Rating |
IP23 |
Dimensions & Weights |
Length, A (mm) |
1910 |
2220 |
2300 |
2770 |
3520 |
Width, B (mm) |
860 |
970 |
1110 |
Height, C (mm) |
1120 |
1490 |
1590 |
1870 |
Dry weight (kg) |
359 |
749 |
820 |
1080 |
1250 |
1340 |
1440 |
1630 |
2300 |
Derating: Given outputs are sea level ratings. Sets should be derated at 1% for every 100m above sea level, and 2% for every 5°C temperature above 20°C for naturally aspirated engines. For turbo charged engines, refer to supplier.