SAR 3



Typical Applications

  • Municipal water distribution - The pump can be  used to supply water in urban and rural areas through municipal water supply systems.
  •  High-rise buildings - Suitable for providing pressurized water to tall structures, ensuring consistent supply across different floors.
  •  Agricultural irrigation - The pump can be employed in farming and agriculture to deliver water to crops, ensuring proper hydration for optimal growth.
  •  Industrial processes - Suitable for transferring liquids in various industrial applications, such as manufacturing processes or chemical plants.
  •  Commercial facilities - Used in settings like hotels, resorts, and commercial buildings to transfer liquids for different purposes.

Operating Conditions

  • Pumped Liquids: Thin, clean, non-explosive liquids without solid particles or fibres.
  • Liquid Temperature Range: -15°C to +120°C
  • Maximum Ambient Temperature: +50°C
  • Maximum Suction Lift: According to the NPSH curve plus a safety margin of 1m
  • Maximum Operating Pressure: 23 bar
  • Maximum Inlet Pressure: SAR3-15 to 29 - 10bar, SAR3-36 - 15bar

Technical Data

Model Motor Full load Current (A) IStart/I Dimensions (mm) Weight (kg)
  Voltage (V) kW HP H1 H2 D1 D2
SAR 3-10 3x415 0.75 1.0 2 5.4 414 649 141 115 26
SAR 3-15 3x415 1.1 1.5 2.2 6.3 504 793 177 141 34
SAR 3-19 3x415 1.5 2 3.5 7 592 887 177 141 40
SAR 3-29 1x240
3x415
2.2 3.0 12.7
4.8
2.6
6.8
772 1067 197 147 45
SAR 3-36 3x415         902 1218 197 147 56