The Dayliff DGC Yanan diesel generators, known for their robustness and high quality, are designed for continuous duty in a wide range of power supply applications. These generators find applications in various industries and settings due to their features and capabilities. Some of the common applications for Dayliff DGC Yanan generators include:
1. Commercial and Industrial Power Backup: The DGC Yanan generators are ideal for providing backup power in commercial and industrial settings. They can ensure uninterrupted power supply during mains power outages, preventing disruptions to critical operations, machinery, and equipment.
2. Construction Sites: The generators are commonly used in construction sites where reliable and continuous power is required. They can provide power for construction equipment, tools, lighting, and other electrical needs on-site.
3. Remote and Off-Grid Locations: DGC Yanan generators are suitable for remote areas or off-grid locations where access to mains power is limited or unavailable. They can be used in remote construction projects, mining operations, agricultural sites, or rural communities, providing a dependable source of power.
4. Healthcare Facilities: Hospitals, clinics, and medical centers rely on continuous power supply for critical equipment, medical devices, and life-saving systems. The DGC Yanan generators can serve as reliable backup power sources, ensuring that healthcare facilities can operate seamlessly during power outages.
5. Telecommunication and Data Centers: Telecommunication towers, data centers, and communication infrastructure require a stable and uninterrupted power supply. The DGC Yanan generators provide backup power in the event of mains power failures, ensuring uninterrupted communication and data services.
6. Residential Backup Power: The generators are suitable for residential backup power applications, providing households with power during blackouts. They can keep essential appliances, lighting, and heating or cooling systems operational, ensuring comfort and safety.
7. Events and Entertainment: The DGC Yanan generators are commonly used for outdoor events, concerts, festivals, or exhibitions. They can power stages, lighting, sound systems, food stalls, and other event infrastructure, ensuring a seamless and uninterrupted experience.
8. Agriculture and Farming: Farms and agricultural operations often require power for irrigation systems, machinery, and livestock facilities. The generators can provide a reliable power source, ensuring continuous operation and productivity in agricultural settings.
Overall, the Dayliff DGC Yanan diesel generators are versatile and reliable power solutions for a wide range of applications. Their robust construction, advanced control features, and dependable performance make them suitable for continuous duty and standby power requirements in commercial, industrial, residential, and remote settings.
Technical Data
Generator Model |
DGC 45C |
DGC 64C |
DGC 80C |
DGC 104C |
DGC 144C |
DGC 200C |
DGC 250C |
DGC 280C |
DGC 320C |
DGC 360C |
DGC 400C |
DGC 460C |
DGC 600C |
DGC 640C |
DGC 800C |
Prime/Standby Power Output |
kVA |
56/63 |
80/88 |
100/110 |
130/143 |
180/200 |
250/275 |
313/350 |
350/375 |
400/438 |
450/500 |
500/550 |
575/650 |
750/825 |
800/888 |
1000/1100 |
kW |
45/50 |
64/70 |
80/88 |
104/114 |
144/158 |
200/220 |
250/280 |
280/300 |
320/350 |
360/400 |
400/440 |
460/520 |
600/660 |
640/710 |
800/880 |
Engine Data |
Type |
Cummins 4BTA3.9-G2 |
Cummins 4BTA3.9-G11 |
Cummins 6BT5.9-G2 |
Cummins 6BTAA5.9-G2 |
Cummins 6CTA8.3-G2 |
Cummins NT855-GA |
Cummins NTA855-G1B |
Cummins NTA855-G2A |
Cummins QSNT-G3 |
Cummins KTA19-G3 |
Cummins KTAA19-G6 |
Cummins KTA19-G3 |
Cummins KTA38-G2 |
Cummins KTA38-G2B |
Cummins KTA38-G5 |
Rated Power @ 1500rpm (kW) |
55 |
70 |
86 |
120 |
180 |
231 |
284 |
310 |
392 |
403 |
448 |
520 |
664 |
711 |
881 |
Max Power @ 1500rpm (kW) |
50 |
80 |
92 |
130 |
163 |
254 |
321 |
313 |
358 |
448 |
504 |
570 |
731 |
790 |
970 |
Aspiration |
Turbo Charged & Aftercooled |
No. of cylinders |
4 |
6 |
12 |
Displacement (L) |
3.6 |
5.6 |
8.3 |
14 |
Fuel Consumptions (litres/hr) |
75% load |
10 |
13.2 |
17 |
23 |
30 |
41.3 |
54.3 |
54.9 |
62.3 |
97 |
107 |
131.5 |
167 |
209 |
100% load |
12.9 |
17.6 |
22 |
30 |
40 |
53.4 |
71.4 |
71.9 |
83.9 |
107 |
121 |
143.5 |
183 |
184 |
228 |
Fuel Tank Size (litres) |
130 |
280 |
330 |
770 |
1212 |
1300 |
1000 |
Use external Fuel tank |
Alternator Data |
Alternator Type |
Self excited 4 pole (1500rpm) single bearing, brushless |
Output Voltage |
3x415V |
Voltage Regulation |
Solid state AVR±1.0% with 4% engine governing |
Insulation Class |
H |
Protection Rating |
IP21 |
Dimensions & Weights |
Length, A (mm) |
2300 |
2800 |
4200 |
4800 |
5800 |
Width, B (mm) |
1100 |
1500 |
1700 |
1900 |
2150 |
Height, C (mm) |
1290 |
1470 |
1800 |
2100 |
2140 |
2340 |
2430 |
2540 |
Dry weight (kg) |
1320 |
1400 |
1600 |
1700 |
4050 |
4250 |
4300 |
4380 |
5500 |
5600 |
6020 |
10350 |
10650 |
Derated : Given outputs are sea level rating.Sets should be derated at 1% for every 100ma bove sea level, and 2% for every 5°C temperature above 20°C. Refer to manufacturer's table for accurate ratings.